Kitchen Ventilation Requirements in NZ: Fans, Ducts, Rules

A New Zealand kitchen needs a mechanical extractor fan or rangehood that vents to the outside. The Building Code’s acceptable solution sets the benchmark at 50 litres per second for a cooktop, including the ducting. An open window does not count, and a recirculating rangehood does not count either. If you are renovating a kitchen, this is a detail to settle in the design stage, because it affects your cabinetry, your wall or ceiling layout and your consent paperwork.
This guide is for homeowners and first-time buyers. It explains which rules apply to you, what the numbers mean in practice, and what to get right before the plasterer and painter arrive.
TL;DR
Kitchens with a cooktop need a mechanical extract fan that discharges outdoors. Under the Building Code’s G4/AS1 the minimum is 50 L/s, including ducting.
Windows alone do not meet the requirement, and a recirculating rangehood is not a ventilation system for compliance purposes.
Healthy Homes Standards apply to rentals, not owner-occupied homes, but if you may rent out your home later, fitting a compliant fan now avoids rework.
Duct to the outside, never into the roof space, and insulate ducting that runs through cold spaces.
Settle the fan, duct route and outlet position in the renovation plan before cabinetry is ordered.
Table of Contents
Which rules apply to a kitchen in your own home
Two sets of rules come up in almost every search on this topic, and they are easy to mix up.
The Building Code, Clause G4 Ventilation. This is the national standard for how buildings are built and altered. G4/AS1 is its acceptable solution, meaning a documented way of showing your work complies. The Fifth Edition took effect on 28 July 2025. It requires mechanical extract fans in household-unit spaces that contain cooktops, showers and baths. If your renovation involves building work that needs a consent, the ventilation in the kitchen is part of what the council looks at.
The Healthy Homes Standards. These are rules for rental homes. Under the Residential Tenancies (Healthy Homes Standards) Regulations 2019, each kitchen and bathroom in a rental must have either an extractor fan or qualifying ventilation, which is a continuous mechanical system. If you live in the house yourself, these do not apply to you. They matter if you plan to rent out a room, a unit or the whole house in future, and they are a sensible yardstick for what a good kitchen fan looks like.
In short: owner-occupiers follow the Building Code when they build or alter, and landlords follow the Healthy Homes Standards as well. The numbers in both are close enough that one good installation can satisfy both.

Why the Building Code insists on mechanical extraction
Cooking releases steam, grease and combustion by-products. In a closed-up New Zealand house in winter, that moisture settles on cold windows, walls and ceilings and feeds mould. BRANZ, the building research body, points out that G4/AS1 itself says natural ventilation on its own is not adequate to remove the moisture produced by cooktops, showers and baths. That is why the acceptable solution names extractor fans as the compliant method for kitchens and bathrooms.
For you, this means a fan is not an optional extra in a kitchen renovation. It protects the new cabinetry, paint and plasterwork you are paying for. Damp air that is not removed shortens the life of all three.
The numbers: airflow, duct size and what they mean
There are two ways the rules describe a compliant kitchen fan: by airflow (litres per second, L/s) or by duct diameter. The table sets out the figures you will see quoted.
Source | Kitchen requirement | Bathroom requirement |
At least 50 L/s, including ducting | At least 25 L/s, including ducting | |
Fan and ducting at least 150 mm diameter, or at least 50 L/s, for fans installed after 1 July 2019 | Same ventilation standard applies to bathrooms | |
Ducted to outside at 50 L/s, or duct at least 150 mm | Ducted to outside at 25 L/s, or duct at least 120 mm |
A few points make these figures easier to use.
The airflow figure includes the duct. A fan that moves 50 L/s on the box but is connected to a long, narrow or kinked duct will deliver less in your kitchen. G4/AS1 counts the flow with the ducting in place, so the route matters as much as the fan.
Watch the units. Fan packaging often shows cubic metres per hour (m³/h) rather than litres per second. BRANZ’s mechanical ventilation bulletin warns that the two are sometimes confused when systems are sized. A worked example: 50 L/s multiplied by 3.6 gives 180 m³/h. A fan rated at 100 m³/h is only about 28 L/s, well short of the benchmark.

Older minimums still appear. BRANZ notes that the old standard NZS 4303:1990 gave 50 L/s intermittent or 12 L/s continuous as the minimum kitchen extract rates, and that 50 L/s is also the G4/AS1 minimum. The 12 L/s figure relates to continuous systems, which are covered further down.
Where the air has to go
The fan is only half of the job. Where it discharges is the other half.
G4/AS1 requires extract air from kitchens, bathrooms, toilets and laundries in household units to go to the outside, with flow rates drawn from the Australian/New Zealand standard AS 1668.2 and discharge meeting its Clause 5.10. In plain terms:
Never into the roof space. BRANZ states that extracted air should always be expelled outside, never into the roof space, where it can cause condensation and mould. A fan that stops a few centimetres above the ceiling lining is a common fault in older homes.
Keep the outlet away from openings. BRANZ advises locating the outlet so that discharged air does not re-enter the home through a fresh air supply, a window or another passive route, and does not enter a neighbouring dwelling. In a townhouse or unit development this is worth checking on the plans.
Insulate cold runs. Ductwork passing through a cold space should be insulated to reduce condensation inside the duct. HomeFit PLUS goes further and recommends R1-insulated, preferably rigid, ducting for new installations.
The same condensation logic applies to the roof structure generally. If you are weighing up roof and ceiling work alongside a kitchen update, this explanation of roof ventilation and condensation shows why moisture should never be left to collect in the roof cavity.
Windows and recirculating rangehoods do not count
Two shortcuts catch out homeowners and first-time buyers.
An openable window. G4/AS1 does require natural ventilation of occupied spaces, with openings of at least 5% of the floor area. But this is a separate requirement. Tenancy Services is clear that openable windows do not replace the kitchen extractor fan or qualifying continuous ventilation. You need both.
A recirculating rangehood. Many rangehoods sold in appliance stores pull air through a charcoal filter and release it back into the room. These remove some grease and odour, but they do not take moisture out of the house. Tenancy Services states that recirculating fans or fans that do not vent outdoors are not suitable for the ventilation standard, though external ducting can enable them to vent outside. If you are buying a house with a rangehood already fitted, look at whether a duct leaves the hood through the wall or ceiling. If there is no duct, it is recirculating.
For first-time buyers, that quick look is useful at open homes. A kitchen without an outdoor-ducted fan is a renovation cost you can plan for and bring up in your offer.
If you rent out the home: the Healthy Homes Standards
Many first-time buyers rent out a room or the whole house at some point, so it helps to know what the rental rule requires.
Each kitchen must have an extractor fan or qualifying ventilation. Fans installed after 1 July 2019 in any room with a cooktop must be at least 150 mm in diameter including ducting, or have an exhaust capacity of at least 50 L/s.
Fans installed before 1 July 2019 have no minimum size or performance requirement, but they must be in good working order and vent to the outdoors.
The landlord’s Healthy Homes statement must record, for each kitchen and bathroom, whether there is an extractor fan or qualifying ventilation, the fan’s diameter or exhaust capacity, and how any qualifying ventilation meets the standard.
Tenancy Services advises landlords to get the fan diameter, ducting and flow rate from the installer in writing so compliance can be shown.
If you are fitting a new kitchen fan anyway, choosing one that meets the 50 L/s or 150 mm benchmark with a proper outdoor duct means your kitchen is already in line with both the Building Code and the rental rules.
Continuous ventilation and exemptions
A continuous mechanical ventilation system can meet the Healthy Homes standard instead of a fan. Tenancy Services explains that it qualifies if it was part of the original building consent first received on or after 1 November 2019 and vents continuously to outdoors. A system added during a renovation can also qualify if it serves several rooms and extracts at least 12 L/s from the kitchen and 10 L/s from the bathroom, with flow able to vary to demand. Recirculating heat recovery or positive pressure systems do not qualify.
There is also a narrow exemption in regulation 24. It applies where no fan existed when the tenancy began, installing one is not reasonably practicable, having none was lawful when the room was built or converted, and any alternative ventilation requirements are still met. The exemption ends if installing a fan later becomes reasonably practicable. A kitchen being fully renovated will rarely fit that description, because the walls and ceilings are open.
The rules changed in 2022 and again in 2025. The May 2022 amendment allowed continuous mechanical systems to comply. From 25 September 2025, the Ministry confirms that Healthy Homes regulations override the older Housing Improvements Regulations 1947 for heating, ventilation and drainage, so compliant landlords do not have to meet both.
Planning kitchen ventilation in a renovation
The cheapest time to get ventilation right is before the cabinetry is ordered. A practical sequence for a kitchen renovation looks like this.
Choose the cooking layout first. An island hob needs a ceiling-run duct, while a wall hob can usually go straight out through the wall. Each gives a different duct length and a different number of bends.
Pick a fan or rangehood rated for 50 L/s with its duct. Look for the airflow in L/s, or convert from m³/h. HomeFit PLUS suggests the rangehood should sit 650 to 900 mm above the hob, which is a good guide for cabinetry heights.
Map the duct route. Keep it short and straight, use the full 150 mm diameter along the whole run, and avoid squeezing it behind cabinets.
Fix the outlet position. It needs to be outside, clear of windows, vents and neighbours’ openings, with a cowl or flap suited to the cladding.
Plan the electrics. The fan needs a power point or a switched supply in the right place, and the electrician should know the position before the walls are lined.
Keep the paperwork. Record the fan model, duct diameter and flow rate. If you rent the house out later, these are the details the landlord’s statement asks for.
Our guide to kitchen appliance planning covers how appliance specifications and Building Code clauses fit together at the planning stage, and the advice on HMR cabinet materials explains why moisture-resistant boards matter in a kitchen. The bathroom has its own extraction needs, which we cover in bathroom heating and extraction.
Common mistakes to avoid
Ducting into the ceiling cavity. It looks tidy and fails the outdoor discharge requirement.
A 100 mm duct on a 150 mm fan. Narrowing the duct cuts airflow and raises noise.
Reading m³/h as L/s. A fan that looks powerful may be well under 50 L/s.
Relying on the window. Natural ventilation and mechanical extraction are separate requirements.
Fitting the fan after the lining is up. Cutting duct routes later often means patching plaster and repainting.
How we handle it
Kitchen ventilation touches several trades: the builder who frames and cuts the openings, the electrician who wires the fan, the cabinetmaker who sets the hood height, and the plasterer and painter who close it up. When these trades are coordinated by one team, the duct route and fan position are decided once and built once. Our kitchens are offered in three grades, A, B and C, and we manage the trades and the building consent process with one point of contact. The details of each grade are on our kitchen pricing page.
If your kitchen is part of a bigger job, such as a whole-house renovation or flood restoration, the same single contact applies across the project through our full home renovation service.

If you are planning a kitchen in Auckland, get in touch with Sorted Home Solutions and we will walk through your layout, the extraction route and the consent steps with you.
Our view on kitchen extraction
Most ventilation problems we see in kitchens are planning problems, not product problems. A good fan on a poor duct run performs like a poor fan. The route, the outlet and the cabinet layout need to be decided together, before the walls are lined. That is why we prefer to run a kitchen as one project with one point of contact. The builder, electrician, plasterer and painter work from the same plan, so the duct is not squeezed in at the end. Fixed-fee quotes and licensed trades mean you know what is included before work begins. For homeowners and first-time buyers, our advice is simple: treat extraction as part of the kitchen design, choose a fan that meets the 50 L/s benchmark with its ducting, and send the air outside. Rudi
FAQ
Do I need an extractor fan in my kitchen in NZ?
In practice, yes. The Building Code’s acceptable solution G4/AS1 requires a mechanical extract fan for spaces with a cooktop, and rentals must have a fan or qualifying continuous ventilation under the Healthy Homes Standards. A window does not replace it.
What size extractor fan does a kitchen need?
The Building Code benchmark is at least 50 L/s including ducting. For rentals, a fan installed after 1 July 2019 needs a diameter, including ducting, of at least 150 mm or a capacity of at least 50 L/s. Check the rating in L/s, as packaging often shows m³/h.
Can a recirculating rangehood meet the requirements?
No. Recirculating hoods do not vent outdoors, so they are not suitable for the Healthy Homes ventilation standard. A rangehood can comply when it is connected to an external duct that discharges outside.
Do Healthy Homes Standards apply if I live in my own house?
No, they apply to rental properties. Owner-occupiers follow the Building Code when building or altering. If you may rent the home out later, fitting a fan that meets the rental benchmark now avoids a second round of work.
Sources